Features
  • 8 contact chambers taking the Han E® power contacts
  • Space-saving and compact design
  • Leading protective ground
  • Crimp terminal with standard Han E® contacts
  • Use of standard tools
  • Insert is suitable for the hoods and housings of the series Han® Q 8/0
  • The contacts can be removed with the aid of a removal tool from the termination side
  • DESINA conform product DESINA is a registered trademark
Specifications
DIN VDE 0627 Connectors and plug-and-socket devices
DIN VDE 0110 table 4 / table 2a for clearances and creepage-distances
DIN EN 61984
Approvals
UL,CSA
 
Inserts
Number of contacts 8 + PE
Electrical data
acc. to DIN EN 61 984

16 A   500 V   6 kV   3
Working current 16 A
Working voltage 500 V
Impulse rated voltage 6 kV
Pollution degree 3
- Pollution degree 2 also 16 A   400 / 690 V  6 kV   2
Working voltage
acc. to UL/ CSA
 
600 V
Insulation resistance > 1010 Ω
Material Polycarbonate
Temperature range - 40 °C ... + 125 °C
Flammability
acc. to UL 94

V 0
Mechanical working life
- mating cycles
 
>
500
 
Contacts
Material
Copper alloy
Surface
- hard-silver plated
- hard-gold plated
3 µm Ag
2 µm Au over 3 µm Ni
Contact resistance
< 1 mΩ
Crimp terminal
- mm²
- AWG
0,5 - 2,5 mm² partly loaded up to 4 mm² is possible
20 – 14
 
Hoods/Housings
plastic
Material
Polycarbonate
RAL 9005
Locking element
Polyamide
RAL
Sealing
NBR
Limiting temperatures
-40 °C / + 125°C
Flammability acc. to UL 94
V 0
Degree of protection
acc. to DIN EN 60529
for coupled connector


IP 65
metal
Material
die cast zinc alloy
Locking element
V2A steel
Sealing
NBR
Temperature range
-40 °C...+ 125°C
Flammability acc. to UL 94
V 0
Degree of protection
acc. to DIN EN 60529
for coupled connector


IP 65
 
Current carrying capacity
The current carrying capacity is limited by maximum temperature of materials for insert and contacts including terminals. The current capacity-curve is valid for continuous, not interrupted current-loaded contacts of connectors when simultaneous power on all contacts is given, without exceeding the maximum temperature.
Control and test procedures according to DIN IEC 60512-5.


Control and test procedures according to DIN IEC 512-3
(1) Wire gauge 2,5 mm²
(2) Wire gauge 1,5 mm²


Harting - Top Industrial Connectors Electronic Connectors Manufacturer in German